Power Quality Analysis in Colorado

Recording what your electrical system is actually doing (sags, swells, transients, imbalance, harmonics and grounding faults) and tracing each problem back to its cause.

When equipment fails without explanation, drives fault, UPS units keep switching to battery or breakers trip with no obvious overload, the cause is usually on the power system, and it is usually intermittent. A meter reading taken on a quiet afternoon won't find it. Power quality analysis records the system continuously, through the full operating cycle, until the event that keeps causing the problem shows up in the data.

What we look for

  • Voltage sags and swells: short dips and rises that reset controls, drop contactors and crash electronics
  • Transients: fast spikes from switching, lightning and capacitor banks
  • Voltage imbalance between phases, which overheats motors long before it trips anything
  • Sustained over- and under-voltage, including transformer tap settings and long feeder runs
  • Harmonic distortion from drives, LED drivers, UPS and charging equipment (covered in depth on our harmonic studies page)
  • Poor power factor and the utility charges that come with it
  • Neutral-to-ground voltage and grounding or bonding faults
  • Flicker and load-driven voltage fluctuation

Symptoms that justify a study

  • Breakers tripping with no traceable overload
  • Drives, PLCs or building controls faulting or resetting
  • UPS systems transferring to battery more often than the utility record explains
  • Motors and transformers running hotter than their loading suggests
  • Lighting that flickers or dims when large loads start
  • Electronics and power supplies failing early
  • Power factor penalties on the utility bill
  • Problems that started after an LED retrofit, new drives, EV chargers or solar were added

Why it comes up in Colorado facilities

Front Range summer thunderstorms make lightning-related transients a real factor, and sites at the end of long distribution feeders outside the metro see more voltage variation than buildings downtown. Many buildings have also added LED lighting, drives, EV charging and solar over a few years without anyone looking at the combined effect.

When the data points to the utility side of the meter, we put it in a form your utility can act on, whether that's Xcel Energy, CORE Electric Cooperative, IREA, United Power or another Colorado provider.

How the analysis works

  • Interview and history: what fails, when, and what changed in the building
  • Recording power quality analyzers at the service entrance and at the affected equipment, typically for 7 to 30 days
  • Event capture triggered on sags, swells and transients, time-stamped so it can be matched to equipment fault logs
  • Voltage, current, power factor, imbalance and harmonic trends across the full operating cycle
  • Grounding and bonding checks, including neutral-to-ground voltage
  • Infrared scanning of distribution equipment where heating is suspected
  • A written report: what we found, what is causing it, and the corrective work in priority order

Findings are classified using the event categories in IEEE 1159, the recommended practice for monitoring electric power quality, so your engineer, your utility and your equipment vendors are all reading the same language.

From findings to fixes

Because we are an electrical contractor and not only a testing firm, the report ends with work we can actually do. That can include surge protection at the service and at sensitive loads, voltage and tap adjustments, load rebalancing across phases, grounding and bonding corrections, ride-through protection for sensitive controls, harmonic filters or reactors, power factor correction, and panel or feeder upgrades where capacity is the real problem. After the correction, we record again to show the problem is gone.

Common questions

What is the difference between power quality analysis and a harmonic study?

A harmonic study looks at one problem in depth: distortion and IEEE 519 compliance. Power quality analysis is broader. It records sags, swells, transients, imbalance, power factor and grounding issues as well as harmonics. If you already know harmonics are the issue, start with a harmonic study. If you only know something is wrong, start here.

Do you have to shut down our equipment?

Usually not. Recording instruments are connected to energized equipment by qualified electricians following NFPA 70E. If a connection point can't be reached safely, we schedule a short outage at a time that suits you.

Can you find the cause of nuisance breaker tripping?

It is one of the most common reasons we are called. Recording current and voltage at the tripping breaker, with event capture, normally shows whether the cause is overload, inrush, ground fault, harmonics or a failing breaker.

Do you do power quality work outside the Denver metro?

Yes. We are based in Parker and do power quality work across Colorado. The recording equipment stays on site for the study period, so outlying sites don't need repeat visits while it records.

Ready to talk about your project?

Tell us what you need and we will give you a straight answer on scope, schedule and cost. No obligation, and no pressure if it turns out we are not the right fit.